Problem: In a room, RGB FCOB LED strips should be used under the ceiling as ambient lighting. The room size is 5m x 4m. A WS28xx FCOB-LED with 720 LEDs/m should be used. The power supply must be placed in the room just a little above the floor, i.e. at a distance of approx. 2 m from the LED strip.
Solution: A total of (5+4)*2 = 18 meters of LED strips must be used. For RGB FCOB strips, the specification 720 LEDs/m means that there are 240 LEDs of each color (R, G, B) per meter. Therefore, as with LED strips with individual LEDs, we count that there are 240 LEDs per meter. At 18 meters there are 18*240 = 4320 "RGB" LEDs. We enter the data into the calculator. At 24 V the voltage drop can be higher, we choose 700 mV:
The result shows that you need a total of almost 18 A and you have to implement 3 power injections: at the beginning, at the end and in the middle. In the middle in this case means in the opposite corner of the room. If you wanted to implement the whole thing with a single power supply, the length of the power lines from the power supply to the respective injection points would be: 2m, 11m, 2m. We use this to calculate the power injections:
It is noticeable that a very thick cable is needed for the middle injection in order to keep the voltage drop small. But it still exceeds 700mV. We therefore decide to place another power supply in the opposite corner of the room. This means that each power supply only supplies half of the LED strip, 4.5 meters in each direction:
This means that each power supply supplies 9 meters of LED strip: 2160 LEDs must be entered into the calculator for each power supply:
The cable from the power supply to the LED strip must have cross section 1.5 mm
2 and be protected with a 10 A fuse. The calculator suggests two power injections, once at the beginning and once at the end of the LED strip. However, our situation is different in that we supply two pieces of LED strips from one power supply, but the power consumption is the same. Therefore, you can use directly the specifications from the calculator regarding injections:
So each power injection is implemented short, must be at least 0.34 mm
2 and is protected with a 5 A fuse:
Four issues can be additionally discussed:
- The 24 V cable on the LED strip must be cut through at the red points. This ensures that no current can flow from one power supply to the other in order to ensure their trouble-free and safe operation.
- The total standby power consumption is approx. 10 watts (see calculator results). Therefore, you should use relays to save electricity and protect the environment.
- The number of “equivalent” physical RGB LEDs is 4320 as calculated above. Since 24 V strips usually have 6 of them in a logical group, the number of logical LEDs is 720. These can all be controlled by a single WLED controller; in the WLED software you specify the number of LEDs as 720.
- The power distribution can be done directly on each power supply, then 4 lines go up from each power supply, i.e. +24V and GND for each 4.5 m LED section (1080 LEDs). For each segment you can calculate this using the calculator as follows:
The whole thing can then be implemented, for example, with a controller, two 24 V relay boards and 4x 5A fuses from
MyHome-Control as follows:
One aspect, namely the negative effect of mass loops, was not covered in this example. Take a look at the next example.
Example 4: 2x 20 meter WS2811 LED strips for a bowling lane; EMC: avoidance of mass loops
Problem: A bowling alley should be illuminated from both sides with an RGB LED strip. The LED strips on both sides should always light up synchronously with one another. The lane is approx. 20 m long and approx. 1 m wide. Since there is already pretty good white lighting, you decide for RGB strips without separate white LEDs. But you would like to have the option of operating the LEDS with full brightness as RGB white too.
Solution: You use WS2811 RGB strips with 30 LEDs/m. This means you have 600 LEDs (=20m*30LEDs/m) per side. If you enter this information into the calculator, the current calculated is 8.13 A per side and it has to be fed in from the front and from the back:
If the power supply is placed at the front, the length of the cable to the rear is approx. 20 meters for each side:
This would require a very high cross-section of the cable (6 mm
2) in order to keep the voltage drop sufficiently low:
An alternative would be to consider a second power supply, which could be placed at the back and would supply the second half of both LED strips directly from there. To do this, you would separate the 12V in the middle of both strips (for safety reasons, so that both power supplies are decoupled):
However, there is still a potential problem to consider: there is a continuous GND connection that basically covers the entire area of the bowling alley. This creates a so-called ground loop, i.e. a low-resistance, large-area loop formed by the ground connection. Such ground loops are problematic from an EMC perspective because they easily introduce interference into the circuit. This can lead to malfunctions in the LEDs. On the other hand, a continuous ground connection of all components is necessary for operation. The problem can be solved, for example, by using a separate power supply for each side at the rear end:
This means that all relevant GND connections remain present, but no ground loop is formed.
Now all cables can be dimensioned. The first power supply at the front (PSU1) supplies two strip halves with 300 LEDs each. The second and third power supplies (PSU2 and PSU3) also power 300 LEDs each. So we calculate the necessary cable and fuse for each half of the strip (300 LEDs each):
A 0.34 mm
2 cable with a 5 A fuse is sufficient. However, the wire section between PSU1 and the power distribution to both LED strips must be dimensioned larger. With a 10 A power supply, the cross section is well dimensioned at 1.5 mm
2 and is typically well protected by the overload protection of the power supply. For more safety or if PSU can deliver more than 10 A current, a fuse can be used here.
For completeness, it can also be added that the data line of the two strips can be connected to a single data output of the WLED controller, as both strips should always work synchronously.
The next picture shows an example of an implementation with a
ABC! WLED Controller (5-24V) and a
fuse board shown: